1. Regular Cleaning
• Physical Cleaning: Every 3-6 months, use a soft brush to remove dirt from the plate surface, avoiding scratches from hard objects.
• Chemical Cleaning: For scale or deposits, use a weak acidic cleaning agent such as citric acid for circulating treatment. Afterward, thoroughly rinse away any remaining liquid.
2. Gasket Inspection and Replacement
• Check the gaskets quarterly for aging, deformation, or cracking. Replace if deformation exceeds 2mm.
• Replacement cycle is generally 1-2 years; under high-temperature conditions, it is recommended to shorten to 8-12 months.
3. Operating Parameter Control
• Pressure: Fluctuations should not exceed ±10% of the design value. Instantaneous overpressure may cause plate deformation.
• Temperature: Control the medium temperature difference within 30℃ to avoid thermal stress causing seal failure.
4. Water Quality Management Optimization
- Install a filter (mesh size ≥ 40 mesh) at the inlet and clean the filter screen regularly.
- Use a water softening treatment system to control the calcium and magnesium ion concentration below 50mg/L.
5. Downtime Handling Plan
• Short-term downtime (<30 days): Evacuate internal media and maintain ambient humidity <60%.
• Long-term downtime (≥30 days): Protect with 0.02MPa nitrogen filling or apply rust-preventive oil to isolate oxygen.
6. Panel Integrity Monitoring
- Inspect panels monthly with fluorescent leak detector. Replace immediately if corrosion spots >0.5mm are found.
- When disassembling for inspection, loosen bolts in an alternating sequence to prevent stress concentration and damage to components.