Plate Heat Exchanger Selection

Nov 04, 2025

Leave a message

This article introduces two selection methods: one is calculation-based selection, and the other is software-assisted selection. The former may be more cumbersome, but the latter is more convenient.

 

(1) Calculation-based Selection

In calculation-based selection, we mainly focus on two flow velocity parameters: the flow velocity of the heat exchanger network and the flow velocity of the unit's main pipe. For the flow velocity of the heat exchanger network, we usually refer to the flow velocity tables of the inlet and outlet water pipes to select appropriate values. For the flow velocity of the unit's main pipe, when the pipe diameter is less than or equal to 80, we can select a flow velocity of 1 m/s; when the pipe diameter is greater than or equal to 100, we also need to refer to the flow velocity table to select an appropriate value.

③ Orifice Flow Velocity: The maximum flow velocity of the four inlet and outlet is limited to 6 m/s.

④ Plate-to-Plate Flow Velocity: The flow velocity varies depending on the type of plate heat exchanger: 0.8 m/s for L-type, 0.6 m/s for M-type, and 0.4 m/s for H-type.

 

2. Calculation and Considerations of Heat Exchange Area

The heat exchange area, i.e., the effective heat exchange zone of a heat exchanger, involves multiple factors in its calculation. The calculation formula is: Heat Exchange Area = Heat Exchange Capacity / Heat Transfer Coefficient / Logarithmic Mean Temperature Difference / Fouling Coefficient. The heat exchange capacity can be calculated using the building area and heating load (i.e., heat capacity). When selecting a specific model, these factors need to be comprehensively considered based on the actual situation to ensure the accuracy and rationality of the selection.

 

3. Medium Parameters:

① District Heating: The temperature range for central heating and geothermal heating is 110/75℃ to 50/75℃ and 110/75℃ to 40/50℃, respectively.

② Building Air Conditioning: The temperature range for fan coil unit heating is 110/75℃ to 50/60℃.

③ Domestic Hot Water: The water temperature range for bathing, kitchens, and laundry rooms is 70/50℃ to 10/55℃.

④ Swimming pool water supply: The temperature range of the constant temperature water supply for the swimming pool is 110/70℃ to 10/40℃.

⑤ High-rise building air conditioning: The temperature range of the chilled water conversion is 7/11℃ to 8/12℃.